TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 78
Parameter
Description
Modbus Address
S
ets the units’ network address
Baud Rate
Set the appropriate baud rate. Possible values (in kbps) are 9.6, 19.2, 38.4, 57.6 or
115.2
Data Bits
The number of data bits is always 8
Stop Bits
The number of stop bits always 1
Parity
The parity is always odd
Table 29. Settings Menu, Modbus RTU Parameters
BACnet MSTP Setup
Selecting BMS Protocol BACnet MSTP from the setup menu shown in
“
Configure
”
button displays
the BACnet MSTP setup menu shown in
Figure 68. Settings Menu, BACnet MSTP Configuration