TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 64
Technician Menu
The Technician menu shown in
is only visible with Technician access level. Refer to
on
Page 43
. Technician menu parameters are shown in
. Note that changing the PI (proportional and
integration) parameters or stage time may result in a hunting phenomenon.
Figure 50. Setpoints Menu, Technician
Parameter
Description
Kp
Set the value for the proportional band of the fan speed PI controller
Ki
Set the value for the integration time of the fan speed PI controller
Stage Time
Time to switch between different operating modes
Table 20. Setpoints Menu Technician Parameters