TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 57
Figure 42. Setpoints Menu, Load Limiting Page 2 of 6
Parameter
Description
Night Quiet
Enable/Disable
Allows use
to either enable or disable the feature. If enabled, the “max fan speed”
and “adiabatic switchpoint” parameters will become active during the times set in
Max Fan Speed
Maximum fan speed that needs to observed when “night quiet” mode is active
Adiabatic Switchpoint
Reduced ambient temperature at which adiabatic operation becomes possible. This
second (reduced versus the standard) adiabatic switchpoint allows adiabatic
operation at lower ambient temperatures in order to make up for the lower available
thermal performance due to the lower fan speed.
Night Quiet Override
If enabled, the “max fan speed” and “adiabatic switchpoint” parameters will become
active regardless of the schedule shown in
. In addition to the on-screen
button, the override can al
so be enabled with the “NightQuietOverride” variable in
Table 65. BMS Communication Points List
Night Quiet Schedule
The schedule defines a start time on one day and a stop time on the next day. All
times are in 24-hour format.
Table 14. Setpoints Menu, Load Limiting Night Quiet Parameters