TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
BMS Communication
Page | 107
12. BMS Communication
BACnet IP & Modbus TCP
BACnet IP and Modbus TCP shall be connected via the RJ45 bulkhead at the bottom on the control panel.
Points List
Variable
Description
R/W
Data
Type
Low
Limit
High
Limit
Modbus
RTU
Registers
BACnet
Addresses
Year
Current Year in YYYY format
R
A
30001
AI1
Month
Current Month in MM format
R
A
30002
AI2
Day
Current Day in DD format
R
A
30003
AI3
Hour
Current Hour in HH format
R
A
30004
AI4
Minute
Current Minute in MM format
R
A
30005
AI5
Second
Current Second in SS format
R
A
30006
AI6
LFT
Leaving Fluid Temperature in x10
format [°C]
R
A
30007
AI7
LFTsetp
Leaving Fluid Temperature Setpoint
in x10 format [°C]
W
A
4.4
50
42049
AV1
CtrlRange
Control Range in x10 format [°C]
W
A
0.5
5.5
42050
AV2
AdiabaticSP
Adiabatic Switchpoint in x10 format
[°C]
W
A
5
50
42051
AV3
OAT
Outside Air Temperature in x10
format [°C]
R
A
30008
AI8
BMSrunEn
BMS Run Enable
0 = Off
1 = On
W
B
2849
BV1
RunStatus
Trillium Run Status
0 = Not Running
1 = Running
R
B
12401
BV2
WaterDisable
Water Usage Disable. Forces the
unit into dry mode
0 = Water Usage Enabled
1 = Water Usage Disabled
W
B
2850
BV3
FanSpdCmd
Fan Speed Command in x10 format
[% max fan speed]
R
A
30009
AI9
ActlFanSpd
Average Fan Speed Feedback in
x10 format [%]
R
A
30010
AI10
ActlFanSpdRPM
Average Fan Speed Feedback in
x10 format [RPM]
R
A
30011
AI11