6-6 Using the Keypad
MN762S
Set P4-02 = 1 to carry out an motor auto tune.
Parameters P4-03 and P4-04 have a significant effect on the behavior of the motor when operating in
vector mode.
The auto tune will begin immediately when P4-02 is set to 1, and no external enable signal is
required. During the auto tune procedure, the motor shaft may turn. It is not normally necessary
to uncouple the load from the motor; however the user should ensure that no risk arises from the
possible movement of the motor shaft.
6.10 Sensorless Vector Torque Control Mode
For applications which require the drive to control motor torque as opposed to motor speed, the drive
can be programmed to operate in Torque Control mode. When operating this way, the drive internal
ramp times (P1-10 and P1-11) are disabled except during starting and stopping.