7-2 Parameter Descriptions
MN762S
Par
No.
Description
Range
Units
Default
Explanation
P1-08
Digital input
function select
0 to 22
-
0
Defines the function of the
digital inputs depending on the
control mode setting in P1-07.
See Tables 5-3, 5-4, 5-5 and
5-6 for more information.
P1-09
Stop mode
select
0: Ramp to stop with
power loss ride
through
1: Coast to stop
2: Ramp to stop with
‘fast stop’ on input
power loss
-
0
0: When the drive enable signal
is removed, the drive will
ramp to stop at the rate
set in P1-11. If the mains
supply is lost, the drive will
try to continue running by
reducing the speed of the
load using the load as a
generator.
1: When the enable signal is
removed from the drive, the
motor will coast (freewheel)
to stop.
2: When the drive enable signal
is removed, the drive will
ramp to stop at the rate set
in P1-11. If the mains
supply is lost, the drive will
ramp to stop using the
P2-25 deceleration ramp
time.
P1-10
Acceleration
ramp time
0.0 to 3000.0
Seconds
5.0
Acceleration ramp time from
0 to base speed (P1-03) in
seconds.
P1-11
Deceleration
ramp time
0.0 to 3000.0
Seconds
5.0
Deceleration ramp time
from base speed (P1-03) to
standstill in seconds. When
set to zero, fastest possible
ramp time without trip is
activated.
P1-12
Energy
Optimizer
0: Disabled
1: Enabled
-
0
When enabled, automatically
reduces applied motor voltage
on light load. Minimum value is
50% of nominal rated voltage
(P1-01).
Table 7-1 Basic Parameters Continued
Содержание VS1MXS51
Страница 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Страница 28: ...5 10 Control Wiring MN762S...
Страница 58: ...7 24 Parameter Descriptions MN762S...
Страница 60: ...8 2 Customizing Your Application MN762S...
Страница 80: ...D 2 Options and Kits MN762S...
Страница 85: ......
Страница 86: ......