Parameter Descriptions 7-19
MN762S
7.4.2 Application Specific Parameters
Table 7-7 Application Specific Parameters - Parameter Group 6
Par
No.
Description
Range
Units
Default
Explanation
P6-01
Software
Upgrade Enable
0: Disable
1: I/O En
2: DSP En
-
0
Enables the Application Macro
loading / firmware upgrade
process.
P6-02
Thermal
Management
Enable
0: Disable
1: Enable
-
0
When set to 1, the drive will
automatically reduce the output
switching frequency with
increasing heat sink temperature,
to reduce the risk of an over
temperature trip.
P6-03
Auto-Reset
Delay Time
1s…60
s
20
Sets the delay time allowed
between consecutive reset
attempts when Auto Reset is
enabled (see P2-17).
P6-04
User Relay
Speed
Hysteresis Band
0.0 … 25.0
%
0.3
This parameter defines a band
around zero speed as a percentage
of P1-03. When P2-11 or P2-13 =
2 or 3, output frequencies below
this value are treated as ‘zero
speed’. This function is used to
prevent “chatter” on the output if
the operating speed coincides with
the level at which the digital / relay
output changes state. E.g. if P2-13
= 3, P1-06 = 50Hz and P6-04 =
5%, the relay contacts close above
2.5Hz.
P6-05
Encoder
Feedback Enable
0: Disabled
1: Enabled
-
0
Enables Encoder Feedback.
P6-06
Encoder PPR
0 .. 10000
-
0
Sets the number of Pulses Per
Revolution for the encoder
P6-07
Encoder Speed
Error Limit
0.0 … 50.0
%
5.0
This parameter defines the allowed
speed error between the encoder
feedback and the VS1MXS own
estimated rotor speed. When set to
zero, the protection is disabled.
Содержание VS1MXS51
Страница 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Страница 28: ...5 10 Control Wiring MN762S...
Страница 58: ...7 24 Parameter Descriptions MN762S...
Страница 60: ...8 2 Customizing Your Application MN762S...
Страница 80: ...D 2 Options and Kits MN762S...
Страница 85: ......
Страница 86: ......