7-18 Parameter Descriptions
MN762S
Par
No.
Description
Range
Units
Default
Explanation
P5-10
Re-Generation
Current Limit
0.0 to 200%
of motor rated
current
%
100.0
This parameter defines the
control current limit when motor
in regenerating mode. The value
in this parameter represents the
percentage value of motor rated
current that is defined in P1-08.
The current limit that defined in
this parameter will override the
normal torque producing current
limit when motor goes into
regeneration mode.
Too high a value may cause big
motor current distortion and the
motor may behavior aggressively
once motor goes into
regeneration mode. The output
torque of the motor may reduce
during regeneration if the value in
this parameter is too small.
P5-11
Pulse Width
Limitation
0...500
(Time = value
*16.67ns)
Ms
-
This parameter is used to limit
the minimum output pulse width,
which can be used for long cable
applications. Increasing the value
of this parameter will reduce the
risk of
over-current trips on long motor
cables, but will also reduce the
maximum available output motor
voltage for a given input voltage.
P5-12
V/F Mode
Magnetizing Period
0…2000ms
ms
-
This parameter is used to set up
a minimum delay time for the
magnetizing current control in
V/F mode when drive run signal
is given. Too small a value may
cause the drive to trip on over-
current if the acceleration ramp is
very short.
Table 7-6 Advanced Parameters Continued
Содержание VS1MXS51
Страница 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Страница 28: ...5 10 Control Wiring MN762S...
Страница 58: ...7 24 Parameter Descriptions MN762S...
Страница 60: ...8 2 Customizing Your Application MN762S...
Страница 80: ...D 2 Options and Kits MN762S...
Страница 85: ......
Страница 86: ......