www.baldormotion.com
7-6 Troubleshooting
MN1943
7.2.7 Tuning
Cannot enable the MotiFlex
e
100 because there is an error 10010:
H
Check the drive enable input on connector X3 pins 9 and 19 is connected and powered
correctly.
When the MotiFlex
e
100 is enabled the motor is unstable:
H
Check that the load is firmly coupled to the motor.
H
Use the Mint WorkBench Drive Setup Wizard to confirm that the correct motor data has been
entered.
H
Use the Mint WorkBench Autotune Wizard to retune the motor.
H
If the motor is still unstable, select the Mint WorkBench Autotune Wizard once more. Click
Options...
. On the Bandwidth tab, move the Current and/or Position and Speed Control
sliders to a slower position to select to a lower bandwidth. Click
OK
to exit and then start the
Autotune Wizard again.
7.2.8 Ethernet
Cannot connect to the drive over TCP/IP:
H
Check that there is not an EPL manager node (for example NextMove
e
100 with node ID
240) on the network. If there is a manager node on the network, then an EPL compatible
router must be used to allow TCP/IP communication on the EPL network.
H
Check that the PC’s Ethernet adapter has been correctly configured, as described in section
6.2.4.
The Ethernet POWERLINK network does not seem to be operating correctly:
H
Confirm that only one device on the network is set to be the Ethernet POWERLINK manager
node (node ID 240, selector switches LO = F, HI = 0).
H
Confirm that the reference source on all controlled nodes has been set to EPL in the Mint
WorkBench Operating Mode Wizard, and that the manager node has been configured
correctly. For a NextMove
e
100 manager node, this requires the System Config Wizard to be
used in Mint WorkBench.
H
Confirm that each device on the network has a different node ID.
H
Confirm that there are no more than 10 ‘daisy-chained’ devices on each branch of the
network.
7.2.9 CANopen
The CANopen bus is ‘passive’:
This means that the internal CAN controller in the MotiFlex
e
100 is experiencing a number of Tx
and/or Rx errors, greater than the passive threshold of 127. Check:
H
12-24 VDC is being applied between pin 9 (+24 V) and pin 6 or 3 (0 V) of the CAN connector,
to power the opto-isolators.
H
There is at least one other CANopen node in the network.
H
The network is terminated
only
at the ends, not at intermediate nodes.
H
All nodes on the network are running at the same baud rate.
H
All nodes have been assigned a unique node ID.
H
The integrity of the CAN cables.
Содержание MotiFlex e100
Страница 1: ......
Страница 2: ......
Страница 60: ...www baldormotion com 3 44 Basic Installation MN1943 ...
Страница 102: ...www baldormotion com 5 28 Input Output MN1943 ...
Страница 136: ...www baldormotion com 7 8 Troubleshooting MN1943 ...
Страница 172: ...www baldormotion com 8 36 Specifications MN1943 ...
Страница 188: ...www baldormotion com B 6 Control System MN1943 ...
Страница 204: ...www baldormotion com C 16 Mint Keyword Summary MN1943 ...
Страница 216: ...Index MN1943 ...
Страница 218: ...www baldormotion com Comments MN1943 Thank you for taking the time to help us ...
Страница 219: ......
Страница 220: ......