Table 7: Modbus register map
Function
Parameter
Description
Range/state
Addr
Data type
Read
only
Test
% value of output, 0~100
2280
Double/float
Output 3
Trim sequence start/
resume live output
2
2300
Integer
Units
Reg. address of meas.
2310
Integer
Type
0 = 4-20mA, 1 = 0-20mA
2320
Integer
Trim reading zero
3.0 ~ 5.2
2340
Double/float
Trim reading span
10.0 ~ 22.2
2350
Double/float
Upper value
-10000 ~ 10000
2360
Double/float
Lower of value
-10000 ~ 10000
2370
Double/float
Test
% value of output, 0~100
2380
Double/float
Alarm
All alarm status
0 ~ 7 (bitfield)
3000
Integer
•
Alarm 1
Status
0 = not tripped,
1 = tripped
3100
Integer
•
Switch
0 = OFF, 1 = ON
3110
Integer
Units
Reg. address of meas.
3120
Integer
Type
Set point = 0,
in band = 1,
out band = 2
3130
Integer
Upper
Depends on unit type
3140
Double/float
Lower
Depends on unit type
3150
Double/float
Alarm 2
Status
0 = not tripped,
1 = tripped
3200
Integer
•
Switch
0 = off, 1 = on
3210
Integer
Units
Reg. address of meas.
3220
Integer
Type
Set point = 0,
in band = 1,
out band = 2
3230
Integer
Upper
Depends on unit type
3240
Double/float
Lower
Depends on unit type
3250
Double/float
Alarm 3
Status
0 = not tripped,
1 = tripped
3300
Integer
•
Switch
0 = OFF, 1 = ON
3310
Integer
Units
Reg. address of meas.
3320
Integer
Type
Set point = 0,
In band = 1,
out band = 2
3330
Integer
Upper
Depends on unit type
3340
Double/float
Lower
Depends on unit type
3350
Double/float
77
Содержание Panametrics Aurora H2O
Страница 2: ...ii...
Страница 4: ...no content intended for this page proceed to next page iv...
Страница 20: ...no content intended for this page 10...
Страница 32: ...no content intended for this page 22...
Страница 65: ...2 AuroraView boots up and displays a screen similar to Figure 55 below Figure 55 AuroraView main screen 55...
Страница 71: ...Figure 74 Exporting a simplified image Figure 75 Selecting enhanced metafile 61...
Страница 80: ...no content intended for this page 70...