INSTALLATION
SETUP AND PHYSICAL INSTALLATION
WBPEEUI230019A0
3 - 3
Dipswitch SW3 Settings
Dipswitch SW3 sets the bus mode and address of the MFP
module. The MFP module can have an address from zero
through 31. Address zero and one should not be used because
other MFP modules will not be able to import data from this
MFP module. All MFP modules within a process control unit
must communicate on the same communication highway
(module bus or Controlway). Table
explains the function of
each dipswitch pole. Table
shows some sample dipswitch
settings. For quick reference, record dipswitch settings in the
user setting portion of the table.
NOTE: Module addresses of redundant MFP modules must be iden-
tical. All modules within a process control unit must be set to com-
municate on either the Controlway or module bus.
Figure 3-1. IMMFP12 Module Layout
P 3
P 2
P 1
T 01 6 04 A
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
ON
ON
S W 4
J U M P E R S A N D P O S T S
M A C H IN E FAU LT T IM E R
S W 3
J1
J2
J3
J4
J5
-3 0 V D C S Y S T E M
(D E FA U LT )
C O N T RO LW AY
R E S E RV E D
R E S E RV E D
J 5
J 5
Table 3-1. IMMFP12 Dipswitch SW3 Settings
Pole
Setting
Function
User
Setting
1
0
Normal run.
1
Invoke diagnostics using dipswitch
SW4.
2
0
Unused. Do not change setting.