IMMFP12 QUICK REFERENCE MATERIAL
INTRODUCTION
A - 2
WBPEEUI230019A0
®
8
0
Primary MFP module.
1
Redundant MFP module.
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. Disabling the checksum routine is sometimes done by development personnel and should never
be done for normal operation. The checksum routine provides additional module integrity and
should be active whenever the module is controlling a process.
2. Leaving this option enabled causes the configuration to be compacted every time the module is
reset thereby increasing the start-up time. This increase becomes more substantial as the size of
the configuration increases. Therefore, do not leave this option enabled longer than necessary.
Disabling this option stops any further compacting operations. It does not uncompact any previous-
ly compacted configuration.
Table A-3. IMMFP12 Jumper J5 Settings
Jumper
Position
Function
1 - 2
Allows the module to function in early Network 90 systems that
supply -30 VDC. Communication is restricted to module bus in
this position.
2 - 3
Allows communication over the Controlway or module bus.
Table A-4. IMMFP12 Module Error Codes
Code
LED
8
7
6
5
4
3
2
1
Condition
01
0
0
0
0
0
0
0
1
NVRAM memory checksum error
02
0
0
0
0
0
0
1
0
Analog input calibration error
03
0
0
0
0
0
0
1
1
I/O module status bad
05
0
0
0
0
0
1
0
1
Configuration error (undefined
block is referenced)
06
0
0
0
0
0
1
1
0
Configuration error (data type mis-
match)
08
0
0
0
0
1
0
0
0
Trip block activated
0B
0
0
0
0
1
0
1
1
NVRAM memory initialized
0C
0
0
0
0
1
1
0
0
NVRAM memory opened for write
operation
0D
0
0
0
0
1
1
0
1
Redundancy link communication
error
0E
0
0
0
0
1
1
1
0
Redundant module IDs are the
same
0F
0
0
0
0
1
1
1
1
Primary module failed, configura-
tion current, secondary module
cannot take over control
10
0
0
0
1
0
0
0
0
Primary module failed, dynamic
data current, secondary module
cannot take over control
11
0
0
0
1
0
0
0
1
Error during write to NVRAM
memory operation
Table A-2. IMMFP12 Dipswitch SW4 Settings
(continued)
Pole
Setting
Function