TROUBLESHOOTING
INTRODUCTION
WBPEEUI230019A0
5 - 3
32
0
0
1
1
0
0
1
0
Address or bus error
Reset MFP module. If error recurs, call
Elsag Bailey field service.
33
0
0
1
1
0
0
1
1
Illegal instruction
Reset MFP module. If error recurs, call
Elsag Bailey field service.
34
0
0
1
1
0
1
0
0
Internal error - trace/
privilege violation
35
0
0
1
1
0
1
0
1
Internal error - spurious/
unassigned exception
36
0
0
1
1
0
1
1
0
Internal error - divide by 0
or check instruction
37
0
0
1
1
0
1
1
1
Any trap instruction
38
0
0
1
1
1
0
0
0
Board level hardware
error
Contact Elsag Bailey field service.
3F
0
0
1
1
1
1
1
1
Normal stop
None.
40
0
1
0
0
0
0
0
0
Backup - cold takeover
ready
80
1
0
0
0
0
0
0
0
Backup - hot takeover
ready
C0
1
1
0
0
0
0
0
0
Primary - operating
XX
1
Unknown
Contact Elsag Bailey field service.
NOTE: 0 = LED OFF, 1 = LED ON.
1.This symbol represents any LED combination not specifically addressed in this table.
Table 5-2. Other IMMFP12 Module LED Conditions
LED
Condition
Corrective Action
Status
OFF
Check power.
Check module seating or try another module mounting unit slot.
If power and seating are okay, remove the MFP module and replace with identi-
cally configured module.
RED
Press stop/reset switch. If LED remains red, remove the MFP module and
replace with identically configured MFP module.
GREEN
None - normal.
7/8
OFF
Check power.
Check module seating or try another module mounting unit slot.
If power and seating are okay, remove the MFP module and replace with identi-
cally configured MFP module.
RED
None - indicates primary module.
8
OFF
Check power.
Check module seating or try another module mounting unit slot.
If power and seating are okay, remove the MFP module and replace with identi-
cally configured MFP module.
RED
None - indicates backup MFP module in redundant configuration.
NOTE: The conditions listed in this table are steady state conditions not transient or temporary conditions.
Table 5-1. IMMFP12 Module Error Codes
(continued)
Code
LED
8
7
6
5
4
3
2
1
Condition
Corrective Action