INTRODUCTION
WBPEEUI230019A0
D
-
1
APPENDIX D - NIMP01/NIMP02 TERMINATION MODULE
CONFIGURATION
INTRODUCTION
The IMMFP12 Multi-Function Processor Module can use the
NIMP01 and NIMP02 termination module for termination.
Jumpers on the NIMP01 module configure the two RS-232-C
ports for data terminal equipment (DTE) or data communica-
tion equipment (DCE). One of the RS-232-C ports can be con-
figured as an RS-485 port. The NIMP02 module is required
when installing redundant MFP modules. Refer to the NIMP01
and NIMP02 product instruction for complete information on
termination module applications.
Figures
through
show the jumper configurations for
jumpers J1 and J2. Figure
shows the jumper for jumpers
J5 through J10. Figure
shows the jumper configurations
for jumpers J14 through J17. Figure
shows the NIMP01
connector and jumper locations. Figure
shows the cable
connections for redundant MFP modules. Figure
shows
the cable connections for a single MFP module.
Jumpers J11 and J12 are storage posts for extra jumpers.
Jumper J13 is normally set with pins one and two connected.
Jumper J18 configures the terminal serial port for RS-485
operation when pins one and two are connected and connector
P7 is used instead of P5.
NOTES:
1.
RS-232-C port connections on the IMP module are through
DB-9 connectors. Use Elsag Bailey cable NKMR02 to connect a
standard piece of equipment (computer or printer with a DB-25 con-
nector) to the IMP module.
2.
There are no jumper settings on the NIMP02 termination mod-
ule. Refer to Figure
for cable connections.