INTRODUCTION
SPECIFICATIONS
1 - 6
WBPEEUI230019A0
®
SPECIFICATIONS
Refer to Table
for the specifications of the IMMFP12
Multi-Function Processor Module.
PCU
Process control unit. A node on the plantwide communication network containing
control and I/O modules.
SAC
Analog control station.
Termination Module
Provides input/output connection between plant equipment and the INFI 90 OPEN/
Network 90 modules.
Termination Unit
Provides input/output connection between plant equipment and the INFI 90 OPEN/
Network 90 modules.
Table 1-3. Glossary of Terms and Abbreviations
(continued)
Term
Description
Table 1-4. Specifications
Property
Characteristic/Value
Microprocessor
32 bit processor (16 bit external bus) running at 16 MHz
Memory
Total
Available
512 kbytes ROM
512 kbytes RAM
256 kbytes NVRAM
347,712 bytes RAM
194,752 bytes NVRAM
Power Requirements
+5 VDC @ 2 A; 10 W typical
Serial Ports
Two RS-232-C ports, or one RS-485 and one RS-232-C port all of
which link signals at a rate of up to 19.2 kbaud.
Station Support
Sixty-four 40-kbaud serial stations (IISAC01) or
eight 5-kbaud serial stations (NDCS03 or NDIS01).
Redundant Communication Link
Rate and Type
1 Mbaud serial link.
Electromagnetic/Radio
Frequency Interference
Values not available at this time. Keep cabinet doors closed. Do not
use communication equipment any closer than 2 meters from the cabi-
net.
Programmability
C, BASIC, BATCH, ladder, function codes, and user-defined functions.
Dimensions
35.56 mm wide (1.40 in.)
177.80 mm high (7.00 in.)
298.45 mm long (11.75 in.)
Mounting
Occupies one slot in a standard INFI 90 OPEN module mounting unit.
Ambient Temperature
0
°
to 70
°
C (32
°
to 158
°
F)
Relative Humidity
5% to 95% up to 55
°
C (131
°
F)(noncondensing)
5% to 45% above 55
°
C (131
°
F)(noncondensing)
Atmospheric Pressure
Sea level to 3 km (1.86 mi)
Air Quality
Noncorrosive
Certification
CSA certified for use as process control equipment in an ordinary (non-
hazardous) location. Factory Mutual approved for use in Class I, Divi-
sion 2, hazardous locations.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.