SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
Repair procedures are limited to module replacement. If the
IMMFP12 Multi-Function Processor Module fails, remove and
replace it with another. Verify that firmware revision levels
match and that the replacement module switch and jumper
settings are the same as those of the failed module.
MODULE REPLACEMENT PROCEDURE
Follow Steps one through five to replace the MFP module.
Observe the steps listed in
when handling MFP modules.
NOTE: Do not remove an MFP module under power unless the
stop/reset pushbutton has been depressed once and the module
has halted (status LED is red and LEDs one through six are on).
This procedure must be followed when removing an MFP module
from a redundant configuration. An operational primary MFP module
must halt operation before control passes to the secondary MFP
module.
1. Turn the two latching screws 1/2 turn either way to release
them.
2. Grasp the screws and pull the module out.
3. Set dipswitches SW3 and SW4 and jumper J5 on the
replacement MFP module to match the settings of the removed
MFP module.
4. Hold the MFP module by the faceplate and slide it into the
slot; push until the rear edges are firmly seated in the back-
plane connectors.
5. Turn the two latching screws 1/2 turn either way to lock
the module into the module mounting unit.
TERMINATION UNIT OR MODULE REPLACEMENT PROCEDURES
To replace a NTMP01 Multi-Function Processor Termination
Unit, NIMP01 Multi-Function Processor Termination Module,
NIMP02 Multi-Function Processor Module, or termination
cable, refer to the NTMP01, NIMP01, or NIMP02 instruction.
These instructions contain step by step replacement proce-