(24) P6–Indoor High Temperature Protection
Explanation of
error
Cause: Protection shutdown due to temperature of indoor coil.
Inspection path: indoor air inlet
→
indoor unit filter
→
indoor motor
→
indoor coil sensor
Tools required
for inspection
Multimeter, pressure gauge, regular 20K
Ω
exhuast sensor (25
℃
)
Frequent
problematic part
1. Check whether the indoor air inlet is blocked or not, if it affects the
wind, remove the shield;
2.Check whether the filter is dirty or not. If dirty blockage is found in
the filter, clean the filter.
3. Check if the air volume at teh tuyere is too small and if the indoor
unit fan is blocked, if is, clean the fan.
4. Measure the drift of the inner disk sensor with a multimeter at
ambient temperature.
Inspection
procedure and
key points
P6 usually refers to the high temperature protection of the Indoor Unit
heating coil due to poor air inlet.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...