54
(23) P5–Exhaust Protection
Explanation of
error
Cause: the exhaust sensor detects that the exhaust temperature is too
high and triggers the exhaust protection shutdown.
Inspection path: system pressure
→
indoor / outdoor air inlet
→
exhaust sensor
→
Outdoor Unit panel
Tools required
for inspection
Multimeter, pressure gauge, regular 50K
Ω
exhuast sensor (25
℃
)
Frequent
problematic part
Indoor coil sensor
Inspection
procedure and
key points
1. Check if the system pressure is low, if is, usually it the shortage of
liquid that leads to excessive exhaust temperature protection;
2. Check whether the indoor/outdoor air inlet is blocked, such as
whether the evaporator or condenser is dirty or whether the filter is
dirty or blocked and if inlet is affected, remove the shield.
3. Check whether the air volume at the teh tuyere is too small, observe
whether the Indoor Unit fan blades are dirty blocked, and if dirty
blocked blades are found, clean the blades.
4. Measure the resistance drift of the exhaust sensor with a
multimeter at ambient temperature.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...