51
(20) P2 -
High-pressure protection
Explanation of
error
Cause: In standby state or when the equipment is running, the
High-pressure switch is disconnected three times (within 20 minutes)
and reported as "High-pressure protection";
Inspection path: High-pressure switch cable
→
connector
→
High-pressure switch
→
main PCB
Tools required
for inspection
Multimeter, connectoin line and High-pressure swtich
Frequent
problematic part
High-pressure swtich connectoin line, fluorine deficiency of unit and
High-pressure swtich
Inspection
procedure and
key points
1. Check whether the plug-in terminals are firmly connected and
whether the terminals and the main PCB are welded loosely. If
necessary, gently pull them to check;
2. Use a multimeter to measure whether it is disconnected;
3. Use the multimeter to check the state of the High-pressure swtich
and check whether it is in the OFF state (normally OFF, unusual
disconnection);
4. If the pressure is normal and the High-pressure switch is kept open,
it is positive that the pressure voltage is faulted;
5. If the pressure switch is normal and the connection line is tact and
the failure is still reported, replace the corresponding main PCB.
Special attention
The reason why High-pressure switches are often disconnected is the
leakage of equipment. When the high voltage switch is off, first check
whether the air conditioner's pressure is normal. If it is normal but the
failure is still displayed aftere replacing the Outdoor Unit main PCB,
it is possible that the connecting pipe may be too long or the Outdoor
Unit ambinet temperature is too low
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...