F6- Outdoor Unit temperature sensor error
Explanation of
error
Cause:
The detection of short circuit or open circuit of Outdoor Unit
termperature sensor during the inspection of Outdoor Unit main PCB,
indicated by "Outdoor Unit termperature sensor error".
Inspection path:
Sensor→Sensor wire→Connectors→Outdoor Unit
main PCB
Tools required
for inspection
Multimeter, 15KΩ standard sensor
(
25
℃
)
Frequent
problematic part
Outdoor Unit temperature sensor, Outdoor Unit main PCB.
Inspection
procedure and
key points
1. Check whether there’s resistance problem, short circuit or open
circuit in the sensor; the resistance value shall be within a reasonable
range (15KΩ under the temperature of 25
℃
).
2. Check whether the sensor wire is broken.
3. Check whether the terminal connectors are well fixed; check
whether the weld between the terminal and the main PCB is loose, and
pull the terminal slightly for inspection if necessary.
4. Check whether the sensor is affected with damp.
5. In case no standard sensor is available at present, replace the
Outdoor Unit temperature sensor with the other sensor asides, and then
check whether the error still exists; if the error disappears, replace the
sensor; if the error still exists, it's possible that the main PCB is faulted,
change the Outdoor Unit main PCB.
Special attention
Most of the standard resistance values of the Outdoor Unit temperature
sensors are 15KΩ (hen temeperature is at 25
℃
), and the higher the
temeprautre is, the lower the resistance value is, and the lower the
temperature is, the higher the resistance value is. Do not use improper
sensor during repairing and maintenance, or it may led to the wrong
temperature sensing of the machine.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...