(13) F4- Exhaust sensor error
Explanation of
error
Cause:
The Outdoor Unit main PCB will indicate “exhaust sensor
error” and send it to the Indoor Unit main PCB when it detects short
circuit or open circuit of the exhaust sensor.
Inspection
path:
Exhaust
sensor→Sensor
wire→Connectors→Outdoor Unit main PCB
Tools required
for inspection
Multimeter, 50KΩ standard exhaust sensor (25
℃
)
Frequent
problematic part
Exhaust sensor, Outdoor Unit main PCB
Inspection
procedure and
key points
1. Check if there is any evident resistance problem in the sensor.
Whether in short circuit or open circuit, the resistance should maintain
in a reasonable range (about 50KΩ when the compressor is not
working and between 3 KΩ and 30 KΩ after the compressor works for
a while, the corresponding exhaust temperature should be 100
℃
-38
℃
).
2. Check if the sensor wire or the sensor connecting wire is damaged.
3. Check if the connecting terminal is connected firmly, the weld
between the terminal and the main PCB is loose; pull the terminal
slightly for inspection if necessary.
4. Check whether the sensor is affected with damp. The coil sensor is
quite easy to be affected with damp in case the lead wire of coil sensor
is above the copper pipe.
5. If there is no standard sensor at hand, exchange the exhaust sensor
with the one beside it to see if the error changes. If yes, there is
something wrong with the sensor and it should be replaced; if it still
indicates “Outdoor Unit coil sensor error”, replace the Outdoor Unit
main PCB.
Special attention
Most exhaust sensors have a standard resistance of 50KΩ (25
℃
). Do
not use improper sensor during maintenance, or the machine will sense
the exhaust temperature mistakenly and enters the protection state
frequently. For example, in the case where replace the 20KΩ coil
sensor for the exhaust sensor by mistake, the exhaust temperature that
the Outdoor Unit main PCB senses will be higher than the actual
exhaust temperature, which will make normal air conditioners enter the
high exhaust temperature protection state frequently, and the
compressor frequency threshold will rise and lead to shutdown of the
compressor.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...