41
(11) F2- PFC protection error
Explanation of
error
Cause:
PFC board is a component of the inverter air conditioner for
power factor correction and voltage boosting. When the PFC board
cannot perform power calibration as normal because of overcurrent and
overvoltage, it will indicate “PFC protection error” and its function
may also be integrated with the module panel or main PCB.
Inspection path:
Supply voltage→AC and DC power path→PFC
board data wire→PFC board→Main PCB
Tools required
for inspection
Multimeter, PFC board in normal condition
Frequent
problematic part
Supply voltage, reactor, PFC board, module panel, Outdoor Unit main
PCB
Inspection
procedure and
key points
1. Check if the supply voltage is unstable and highly volatile or the
voltage is too low (below AC 135V)
2. The reactor is one of core parts of PFC. Check if the reactor itself is
destroyed and the reactor connecting wire is in poor connection, which
makes PFC functions not performed. Do not remove the reactor and
replace with short circuit by no means.
3. If “PFC protection error” will be indicated immediately after starting
up, it is almost certain that it’s substantial error, having nothing to do
with supply voltage, it is suggested to observe if there is any
component destroyed by strike arc near the module panel
4. Test if the 15V and 5V (3.3V) power supply on the PFC board is
stable and exclude the PFC board error caused by power supply of the
Outdoor Unit main PCB.
5. Replace with the PFC board in normal condition for test. If the test is
normal after changing the PFC board, then the original PFC board is
destroyed.
6. The possibility that there is something wrong with 15V or 5V power
of the module panel that causes the control power supply problem of
the PFC board is not excluded.
7. Some module panels integrate PFC function and compressor drive
function in one, so just replace with an integrated module panel.
8. For single-panel single-chip main PCBs, if PFC protection error
appears, and there is no problem in supply voltage, reactor connection
or reactor, just replace the controller of the Outdoor Unit.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...