31
(
3
)
E2 -Outdoor Unit coil sensor error
Explanation of
error
Cause:
The detection of short circuit or open circuit of Outdoor Unit
coil sensor during the inspection of Outdoor Unit main PCB, indicated
by “Outdoor Unit coil sensor error”.
Inspection path:
Sensor→Sensor wire→Connectors→Outdoor Unit
main PCB
Tools required
for inspection
Multimeter, 20KΩ standard sensor (25
℃
)
Frequent
problematic part
Outdoor Unit coil sensor, Outdoor Unit main PCB
Inspection
procedure and
key points
1. Check whether there’s resistance problem, short circuit or open
circuit in the sensor; the resistance value shall with a reasonable range
(about 20KΩ for frequency conversion machine)
2. Check whether the sensor wire is broken.
3. Check whether the terminal connectors are well fixed; check
whether the weld between the terminal and the main PCB is loose, and
pull the terminal slightly for inspection if necessary.
4. Check whether the sensor is affected with damp. The coil sensor is
quite easy to be affected with damp in case the lead of coil sensor is
above the copper pipe.
5. In case no standard sensor is available at present, replace the
temperature sensor of Outdoor Unit coil by other sensor asides, and
then check whether the error still exists; if the error disappears, replace
the sensor; if the error still exists, check the Indoor Unit main PCB and
change if necessary.
Special attention
Most Indoor Unit temperature sensors of the frequency conversion
machine have a resistance value of 20KΩ.
Do not use improper sensor during repairing and maintenance, or it
may led to the start of protection mode due to wrong temperature
sensing of the machine, or the protection error.
In case a sensor with the resistance value over 20KΩ is used, the
detected temperature will be much lower than the actual temperature,
which may lead to the frequent entering of defrost mode, the illusory
defrosting or the protection error during the cooling process.
In case a sensor with the resistance value below 20KΩ is used, the
detected temperature will be much higher than the actual temperature,
which may lead to defrost error during the heating process, or the start
of protection during the cooling process.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...