(22) P4 –Refrigeration Overload Protection
Explanation of
error
Cause: Outdoor coil sensor senses excessive temperature, prevents
compressor from overloading, and reduces frequency.
Inspection path: the system is dirty or blocked
→
the condenser is
dirty
→
Outdoor Unit coil sensor is faulated
→
AC motor not running
→
failure of divider resistance of controller
Tools required
for inspection
Multimeter and pressure gauge
Frequent
problematic part
Coil sensor, condenser and outdoor unit controller
Inspection
procedure and
key points
1. Check the coil sensor with a multimeter to see if the resistance value
is normal (20KΩ standard sensor, 25
℃
)
2. Use a pressure gauge to detect system pressure. If the system
pressure is high, it may cause Indoor Unit dirty blockage or poor
Outdoor Unit heat transfer, which may lead to high coil temperature.
3. Observe whether the speed of AC motor is too low, which leads to
poor heat transfer and high coil temperature.
4. Use a multimeter to check whether the voltage dividing resistance of
temperature sensor circuit of Outdoor Unit controller coil is abnormal.
If you don't know how to measure it, try to replace the Outdoor Unit
controller to check whether it returns to normal state.
Содержание ASW-H09B5B4/FAR3DI-C3
Страница 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Страница 2: ...This manual is for professional maintenance personnel only ...
Страница 4: ...1 Part I Technical Information 1 Summary 1 1 Appearance Indoor Unit FZ Outdoor Unit 09K 12K 18K 24K ...
Страница 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Страница 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Страница 18: ...15 18K 24K ...
Страница 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Страница 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Страница 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Страница 74: ...71 9 2 Outdoor Unit ...
Страница 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Страница 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Страница 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Страница 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Страница 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Страница 82: ...79 2 Remove top cover 3 Remove control box cover ...
Страница 83: ...80 4 Remove panel grille 5 Remove front panel ...
Страница 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Страница 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Страница 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Страница 87: ...84 12 Remove reactor 13 Remove partition board ...
Страница 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Страница 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...
Страница 90: ...87 18 Remove compressor 19 Remove condenser ...