Note:
H = Height of Outdoor Unit
-
Height of Indoor Unit
Different Heating Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit
-
Height of Indoor Unit
3.5 Correction capability
Cooling capacity = nominal cooling capacity xK1xK3
Heating capacity = nominal heating capacity xK2xK3
3.6 Equivalent Pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate the pressure loss.
1. Bend and Oil Loop Conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
H
e
ight
D
iff
erenc
e
H
(m
)
C
oo
ling
Equivalent pipe length EL (m)
H
e
ight
D
iff
erenc
e
H
(m
)
Equivalent pipe lengthEL(m)
H
eat
ing
Содержание AMCA-H09/4R1A
Страница 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Страница 28: ...AUX DC Inverter Free Match 50HZ R410A Ceiling Floor Type 28 4 Dimension AMCF H09 4R1 AMCF H12 4R1 AMCF H18 4R1 ...
Страница 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Страница 106: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 106 Communication failure between indoor and outdoor unit ...
Страница 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Страница 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Страница 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Страница 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Страница 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Страница 112: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 112 Cooling exhaust temperature protection ...
Страница 113: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 113 Heating exhaust temperature protection ...
Страница 114: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 114 Refrigerant shortage or four way valve failure protection ...
Страница 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Страница 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Страница 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Страница 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Страница 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 122 Air switch action when air conditioner starting up ...
Страница 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Страница 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Страница 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...
Страница 134: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 134 Installation of wired controller ...