AUX DC Inverter Free Match 50HZ R410A
Ceiling & Floor Type
27
Bend and Oil Loop Conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent Pipe length L
=
Actual Pipe length L+ Bend Qty× Equivalent pipe bend Oil Loop
Qty × Equivalent Oil Loop length
Sample:
AMCF-H09/4R1Actual Pipe length is 25 meters, Gas pipe diameter is 9.52
mm. If there’s 5 bends and
2 oil loops during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
◇
Specification of Connection Pipe for Indoor Unit and Outdoor Unit
Cooling Capacity(Btu/h)
9000
12000
18000
Connection
Pipe (mm)
Liquid Pipe
Φ6.35
Gas Pipe
Φ12.7
Max. Length(Each)
15
Max. Height (m)
10
Max. Bend Qty
5
Extra R410a per meter when the pipe
length is more than 5 meter (kg)
0.022
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is
necessary. If the pipe length is more than this then you should charge more refrigerant into the system
according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased. And the
more bend quantity, the resistance in the piping system would be bigger, then the cooling and heating
capacity would be decreased even lead to compressor broken. We suggest you to use the shortest
connection pipe according to the pipe length parameter in this manual.If the height difference between
outdoor and indoor unit is more than 5m, an oil trap should be installed in the gas pipe for every 10
meters.
Содержание AMCA-H09/4R1A
Страница 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Страница 28: ...AUX DC Inverter Free Match 50HZ R410A Ceiling Floor Type 28 4 Dimension AMCF H09 4R1 AMCF H12 4R1 AMCF H18 4R1 ...
Страница 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Страница 106: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 106 Communication failure between indoor and outdoor unit ...
Страница 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Страница 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Страница 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Страница 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Страница 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Страница 112: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 112 Cooling exhaust temperature protection ...
Страница 113: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 113 Heating exhaust temperature protection ...
Страница 114: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 114 Refrigerant shortage or four way valve failure protection ...
Страница 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Страница 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Страница 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Страница 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Страница 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 122 Air switch action when air conditioner starting up ...
Страница 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Страница 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Страница 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...
Страница 134: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 134 Installation of wired controller ...