AUX DC Inverter Free Match 50HZ R410A
Four-way cassette
11
3. Capacity Amendment
3.1 Running range
Cooling capacity (Btu/h)
9000
12000
18000
Power supply
220-240V~/50Hz
Voltage
187~253V
Ambient
temperature
Cooling
-10~52
℃
Heating
-15~24
℃
3.2Amendment coefficient of cooling capacity under different indoor/outdoor
temperature(
K1)
Indoor
temperature(
℃)
Outdoor temperature(
DB)
DB
WB
25
30
35
40
45
50
22
15
0.97
0.92
0.87
0.96
0.77
0.75
24
17
1.03
0.98
0.94
0.89
0.84
0.80
27
19
1.10
1.05
1
0.95
0.90
0.86
29
21
1.16
1.11
1.06
1.02
0.96
0.91
32
23
1.22
1.17
1.13
1.08
1.02
0.98
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.3 Amendment coefficient of heating capacity under different indoor/outdoor DB/WB
temperature K2
Outdoor temperature(
℃
)
Indoor temperature(
DB)
DB
WB
15
20
25
-15
-16
0.64
0.59
0.55
-10
-12
0.71
0.66
0.62
-7
-8
0.76
0.72
0.67
-1
-2
0.79
0.74
0.70
2
1
0.81
0.76
0.72
7
6
1.04
1
0.96
10
9
1.10
1.06
1.01
15
12
1.16
1.12
1.07
Actualheatingcapacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
Содержание AMCA-H09/4R1A
Страница 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Страница 28: ...AUX DC Inverter Free Match 50HZ R410A Ceiling Floor Type 28 4 Dimension AMCF H09 4R1 AMCF H12 4R1 AMCF H18 4R1 ...
Страница 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Страница 106: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 106 Communication failure between indoor and outdoor unit ...
Страница 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Страница 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Страница 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Страница 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Страница 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Страница 112: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 112 Cooling exhaust temperature protection ...
Страница 113: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 113 Heating exhaust temperature protection ...
Страница 114: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 114 Refrigerant shortage or four way valve failure protection ...
Страница 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Страница 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Страница 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Страница 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Страница 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 122 Air switch action when air conditioner starting up ...
Страница 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Страница 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Страница 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...
Страница 134: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 134 Installation of wired controller ...