AUX DC Inverter Free Match 50HZ R410A
Installation
87
8. Installation
8.1 Preparation and equipments before installation
1
Please buy following spare parts from your local market before installation
2
Hung bolts M12, 4 pcs
3
Drainage pipe PVC
4
Copper connecting pipe
5
Adhesive belt (big size) 5 pcs, (small size) 5 pcs
6
Heat insulation material used to connect copper pipe (PE foam material, its thickness is more than 8mm)
7
Power cable, electrical wire between indoor and outdoor unit(Must be in accordance with the wire diameter
in the wiring diagram)
8
Acetylene cylinders, oxygen cylinders (when longer pipe used it should be welded)
9
One set pipe cut machine. (cut copper pipe)
10
Refrigerant cans, electronic balance (when longer pipe used additional gas should be charged)
11
Pressure gauges, pipe clamp, welding torch, 2B silver electrode
12
Wrench 2 pcs, one of them is with adjustable torque wrench(42N.m,65N.m,100N.mm)
13
Nitrogen cylinder (in order to prevent oxidation when welding, using Nitrogen to replace the air)
Select installation position of outdoor unit
◇
The site shall be strong enough to bear its weight, prevent noise and vibration.
◇
The site shall be ensured to avoid direct sunshine, if necessary set a Havelock above the outdoor unit.
◇
The site shall be easy to drainage the rain water and the frost water.
◇
The site shall be ensured that the outdoor unit will not be covered by snow LDring the winter season.
◇
The site shall be ensured that the outlet is not facing the strong wind.
◇
The site shall be ensured that outlet air and
operation noise will not affect the neighbors’ daily life.
◇
The site shall be ensured that the outdoor unit will not be affected by the garbage and oil mist.
Warning :
If outdoor unit working under such environment which contains oil (including machine oil) salt(marine areas), sulfide
gas (hot springs and oil refinery areas), those substance may lead to the failure work of the outdoor unit.
Maintenance and ventilation space
◇
The site shall be easy for ventilation then the outdoor unit can inhale and dischar
ge air easily. What’s more please
reserve enough space for maintenance.
Note: Require A
>
300mm; B
>
1500mm; C
>
300mm; D
>
500mm;
Outdoor unit installation
◇
Use size M10 bolt and nut to fasten the outdoor unit tightly on the bracket, keep it in the horizontal level. The
suitable length for bolt shall 20mm over the base level, in order to minimize vibration please do set a rubber shock
absorber.
◇
If the outdoor unit is mounted on the wall or on the rooftop, in order to prevent earthquake and strong wind please
fasten it as tightly as possible.
◇
Set a drainage channel to ensure the condensing water can drain out smoothly.
Содержание AMCA-H09/4R1A
Страница 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Страница 28: ...AUX DC Inverter Free Match 50HZ R410A Ceiling Floor Type 28 4 Dimension AMCF H09 4R1 AMCF H12 4R1 AMCF H18 4R1 ...
Страница 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Страница 106: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 106 Communication failure between indoor and outdoor unit ...
Страница 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Страница 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Страница 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Страница 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Страница 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Страница 112: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 112 Cooling exhaust temperature protection ...
Страница 113: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 113 Heating exhaust temperature protection ...
Страница 114: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 114 Refrigerant shortage or four way valve failure protection ...
Страница 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Страница 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Страница 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Страница 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Страница 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 122 Air switch action when air conditioner starting up ...
Страница 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Страница 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Страница 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...
Страница 134: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 134 Installation of wired controller ...