AUX DC Inverter Free Match 50HZ R410ALow ESP Ducted type
45
6.7 Drainage pipe
◇
Drainage pipes must be wrapped with heat insulation materials, otherwise it will cause frost or droplets, see picture
as follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the pipeline fluently,
and carefully observe the junction to ensure that there is no water leakage at the junction. If the unit is installed in
the newly built house, strongly recommend that this test taken before the CFiling installation. Even it is the heating
only unit, this test is unavoidable.
6.8 Remote controller receiver
◇
Installation site: recommend that the receiver is mounted with the distance of 30~50 cm to the indoor unit air
outlet(on your choice as well), while must ensure that the receiver can get the signal that the remote controller
sends, please refer to the following installation picture:
◇
Mounting hole set up: please use certain instrument to dig a square hole with 88*88mm on the ceiling
◇
Remote controller receiver installation.
Hold the two sides (with clip sides) of the receiver, set the spring clip in the vertical way then put it into
the mounting hole, if the two sides of the receiver is in the same level with the ceiling the installation is finished.
Содержание AMCA-H09/4R1A
Страница 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Страница 28: ...AUX DC Inverter Free Match 50HZ R410A Ceiling Floor Type 28 4 Dimension AMCF H09 4R1 AMCF H12 4R1 AMCF H18 4R1 ...
Страница 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Страница 106: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 106 Communication failure between indoor and outdoor unit ...
Страница 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Страница 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Страница 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Страница 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Страница 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Страница 112: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 112 Cooling exhaust temperature protection ...
Страница 113: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 113 Heating exhaust temperature protection ...
Страница 114: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 114 Refrigerant shortage or four way valve failure protection ...
Страница 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Страница 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Страница 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Страница 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Страница 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 122 Air switch action when air conditioner starting up ...
Страница 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Страница 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Страница 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...
Страница 134: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 134 Installation of wired controller ...