COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
r
Logical Inputs / buttons
The
Logical Inputs
tab contains all available buttons as well as logical inputs on the AutroVoice miniVES central unit. The first
four items in this section are buttons located on the front panel of the AutroVoice miniVES. The next seven inputs are
located on the charger module. Lastly, there are two additional inputs located on the xNet_mini communications card
in the xxxxN series devices. A double click on the name of a button / logical input enables to change the generic name
assigned by the configurator.
t
Logical Inputs / Events
The
Events
buttons transfers the programmer directly to the
EventConfiguration
tab. This enables to assign any function or
event group to a selected button. A right-click on the name of a button / logical input in the
EventConfiguration
tab, as well
as selection of
Go to definition
, enables to return quickly to the editing menu of the
Central Unit
.
y
Logical Inputs / Mode
The logical input editing window enables activation of the input monitoring function –
Mode Contact
/
Monitor
. In case the
Monitor
option is selected, it is necessary to install two 4.7 kΩ parametrizing resistors at the end of the line. In the window
Default
, we select the input status for inactivity for the
NC
option the system expects a closed circuit, opening the circuit
results in activation of the function assigned in
EventCongifuration
. For
NO
the situation is reverse: the system expects an
open circuit on the input, closing results in activation of the assigned function.
u
Logical Output / Name
The
Logical Outputs
tab contains all available logical (relay) outputs on the AutroVoice miniVES central unit. A double click
on the name of a logical output enables to change the generic name assigned by the configurator. Assigning a function to
a chosen relay is possible in the
EventConfiguration
– select an input event, assign a general function and click
Add control
outputs
action (the circle in a square icon
).
i
Logical Output / Settings
The relay type window informs about the physical type of the relay installed.
NC
– normally closed, in case of a power cut,
the relay will be closed,
NO
– normally open, in case of a power cut, the relay will open. The
Mode
window enables to reverse
the relay logic, opposite to its behaviour in case of a power cut. The
Inverse
causes, e.g., that the relay
NC
/
Inverse
– in the
original status it is a NO relay, and activation of the function to which it is assigned will change the status of the relay into
the opposite one, i.e. NC. For
NC
/
Normal
in the original status (not triggered by any function) the relay is closed, activation
of the function, as assigned to this output, causes that the relay status changes into the opposite one, i.e. open. The values
from the windows
Relay Type
and
Mode
are also duplicated in the information window below
Scenario State
and in the
EventConfiguration
tab the function
General
–
Logical Outputs
, also in the information window below
State
.
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...