COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
12.3.10 xCtrLine-2 / 4
1
HV Audio Inputs
The name field enables to assign an individual name to the input intended to receive a 100 V signal from an amplifier output.
The name is shown on the main AudIO-4/12 editing window, in the
Connection
tab.
2
SubZones / Mode:
Mode
enables switching the card into following modes:
Loop
– the system detects short circuit / open line as well as ground
leakage;
Regulator
– the volume control mode on the speaker line.
3
SubZones
Speaker zone editing window. It enables changing of the generic name of a zone by double-clicking the name. In addi-
tion, it is possible to define which speaker line outputs (A,B,C,D) are assigned to a given zone. Any combination is possible,
however the default settings are accordant with the EN54-16, EN54-4 standards and assign two outputs per each zone.
4
Line Control Configuration / Control Method:
Speaker line supervision method window – options include:
Impedance
method and
Switching off
the speaker line supervision.
5
Save Rev.
If the system is supposed to supervise speaker lines by means of the
impedance method
, having loaded a configuration into the
system and connected a speaker line of a properly matched power and free of ground faults, load the impedance reference for
a given line. In order to do this, select the
Save REV
button. From now on, the system properly supervises the operation of the speaker
line. The
impedance method
continuously measures the impedance of the speaker line and if the value set in the tolerance window
has been exceeded, an error is reported. The
impedance method
is equipped with a number of algorithms to minimize reporting
untrue faults resulting from abrupt temperature changes which affect line impedance, as well as sudden changes of impedance itself.
Adequate impedance measurement range on a single speaker line starts at 12.5 Ω, and ends at 10 kΩ, for measured frequency of
20 kHz. A 4-output xCtrLine-4 card (A,B,C,D) can be loaded up to 800 W of total power, the maximum load for a single speaker line is
300 W. In the case of a bridged connection of outputs A+B and C+D, the maximum tolerated power for each pair is 450 W. for a 2-out-
put xCtrLine-2 card (A,B), the correct impedance measurement range on a single speaker line is minimum 12.5 Ω, max 10k ohm, for
the reference frequency of 20 kHz. A 2-output card can be loaded up to 400 W of total power, the maximum load for a single speaker
line is 300 W. In the case of a bridged connection of outputs A+B and C+D, the maximum supported power for each pair is 450 W.
6
On-line mode
The on-line mode enables to view the impedance values, as measured, as well as record reference impedance into the control
card. Having loaded a configuration into the system, a single click on the left mouse button on the grey icon results in
entering the real-time view mode and change of the colour of the icon into bright green . A change of tolerance, reference
impedance or real-time measurement must be preceded by entering into the on-line mode.
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...