101
In the window
Default
, we select the input status for inactivity for the
NC
option the system anticipates a closed circuit on the
input, opening results in activation of the function assigned in
EventCongifuration
. For
NO
the situation is reverse: the system
anticipates an open circuit on the input, closing results in activation of the assigned function.
6
Logical Outputs
The
Logical Outputs
tab contains all available logical (relay) outputs on the fireman microphone. A double click on the name
of a logical output enables to change the generic name assigned by the configurator. Assigning a function to a chosen relay
is possible in the
EventConfiguration
– select an input event, assign a general function and click
Add control outputs
action
(the circle in a square icon
).
7
Relay Type / Mode
Relay type
is a window to inform of the physical type of the relay installed.
NC
– normally closed, in case of a power cut,
the relay will be closed,
NO
– normally open, in case of a power cut, the relay will be open.
The
Mode
window enables to reverse the relay logic, opposite to its behaviour in case of a power cut. The
Inverse
causes,
e.g., that the relay
NC
/
Inverse
– in the original status it is a NO relay, and activation of the function to which it is assigned
will change the status of the relay into the opposite one, i.e. NC. For
NC
/
Normal
in the original status (not triggered by
any function) the relay is closed, activation of the function, as assigned to this output, causes that the relay status changes
into the opposite one, i.e. open. The values from the windows
Relay Type
and
Mode
are also duplicated in the information
window below
Scenario State
and in the
EventConfiguration
tab the function
General
–
Logical Outputs
, also in the infor-
mation window below
State
.
8
Audio input options
Activating the
play after record
option allows recording up to 40 s of a message being transmitted by the ABT-DFMS and
playing it back immediately after releasing the PTT button.
Max time
– sets the length of recorded message.
Max delay
– sets the longest time the system will wait for the intended transmission zone to be freed. After the set time the
message will be played back from the buffer. If the operator chooses to transmit to more than one zone, the system will
play the message in all the available / free zones after the set delay time has passed and erase the message from the buffer.
9
On-line mode
The online mode offers the user the possibility to view the audio level meter in real time and to adjust the mic volume
level. After uploading the configuration into the system, you can enter the on-line mode by clicking the icon
– it will then change it’s color to green indicating active on-line mode .
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...