91
3
System Connection / Upload (PC -> System)
This allows to send a configuration, created on a PC running the configurator software to the AutroVoice miniVES system
connected to that PC. Prior to sending the configuration to the system, the software verifies the configuration file.
Upload full
configuration
– sends the entire configuration from the PC to the system, including audio files in the PCM format. Loading of
a full configuration must be executed for the first time an empty system is being programmed, every successive configura-
tion change which does not require changes in audio files may be loaded into the system via
Upload configuration without
audio
which makes programming of the system much faster.
4
System Connection / Download (System -> PC)
This allows to download the current full system configuration or the configuration prior to the current one from system into a PC.
5
System Connection / Recreate Topology
This function reads the system architecture. The system is able to identify cards located on a particular slot of the control
unit, it detects all zone and fireman microphones connected and the method and place of connection of the units and
microphones (optical fibre, cat5).
Caution:
the only element which is not detected by the system recreating topology
are microphone extensions.
6
System Connection / Change password
Allows to change the previously set password needed to upload the configuration to the system. The change is authorized
either by entering the previous password or by generating a token. The token is created by Autronica after received a five
digit code generated by the Control Unit GUI (applies only to units equipped with LCD screens).
7
System connection / Sync system UTC with local
This option synchronizes the system’s internal clock with the time on the computer running the configurator software.
8
System Connection / Blackbox
The
Blackbox
function records audio from all connected DFMS fireman microphones while the alarm mode is active.
Download blackbox buffer
retrieves the data stored in the microphones.
Clear blackbox buffer
- erases all the messages
recorded during alarm mode.
9
System Connection / Record message
If this function has been enabled in the system you can download the messages recorded by DFMS, DMS or DMS-LCD
microphones by clicking
Download record message buffer
.
Clear record message buffer
deletes all the messages.
q
Project signature
The
project signature
acts as a key which is needed for remote server access. If the system is set up correctly and the
configuration has been sent to all the devices, the project signature should be sent to the remote access server administrator.
NOTE:
After changing the signature the server with remote access will no longer be able to connect. The access rights are
assigned to the administrator (key), but also to a specific system with given signature.
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...