83
11.2.3 Annual inspection
All maintenance works included in the 6-month inspection apply here, yet additionally:
W
Perform sound pressure level tests in randomly selected areas of the building in order to verify if there are no changes
causing a decrease of parameters below the required values by EN 60849 norm.
W
Check if impedance of particular loudspeaker lines is in compliant with the blueprint.
W
Check alarm message scenarios sent by FAS
W
Measure battery capacity – if the capacity dropped below 80% of the design capacity, batteries must be replaced.
W
Safety inspection must be carried out frequently, at least every 12 months; the manufacturer recommends to take
maintenance actions every 6 months.
11.2.4 Manufactures remarks
Please note that Autronica is not responsible for results of unauthorized repairs.
Any repairs of the equipment should be carried out by the Autronica or a service centre authorized by Autronica.
In any unresolved issues, please contact Autronica trained personnel. Content contained herein is subject to change without notice.
Autronica reserves the right to change or modify the product and conditions applicable to the use of this product at any time.
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...