F
3-
-1
6A
D
16
-C
ha
nn
el
A
na
lo
g
In
pu
t
5--4
F3--16AD 16-Channel Analog Input
As you examined the jumper settings, you may have noticed there are current
jumpers for each individual channel. These jumpers allow you to select the type of
signal (voltage or current).
The span and polarity jumpers are used to select the signal range. The polarity and
span selection affect all the channels. For example, if you select unipolar operation
and a 10V span, you can use both 0 --10V and 0--20 mA signals at the same time.
Channels that will receive 0--20 mA signals should have the current jumper installed.
The following table shows the jumper selections for the various ranges. (Only
channel 1 is used in the example, but all channels must be set.)
Bipolar Signal Range
Jumper Settings
--5 VDC to +5 VDC
--10 VDC to +10 VDC
Unipolar Signal Range
Jumper Settings
0 to 20 mA
(these settings are also used
for the 4--20mA range)
0 VDC to +10 VDC
Selecting Input
Signal Ranges
Polarity
Uni
Bi
Current Jumper
Span
10V
20V
Polarity
Uni
Bi
Current Jumper
Span
10V
20V
Polarity
Uni
Bi
Current Jumper
Span
10V
20V
Polarity
Uni
Bi
Current Jumper
Span
10V
20V