D
3-
-0
2D
A
2-
C
ha
nn
el
A
na
lo
g
O
ut
pu
t
6--2
D3--02DA 2-Channel Analog Output
Module Specifications
The following table provides the specifications for the D3--02DA Analog Output
Module. Review these specifications to make sure the module meets your
application requirements.
Number of Channels
2 (independent)
Output Ranges
0 -- 10V, 4 -- 20 mA
Resolution
8 bit (1 in 256)
Output Type
Single ended
Output Impedance
.5
O
maximum, voltage output
Output Current
10 mA minimum, voltage output @ 10 VDC
Load Impedance
550
O
maximum, 5
O
minimum, current output
Total Inaccuracy
?
0.4% maximum at 25
_
C
Accuracy vs. Temperature
?
50 ppm /
_
C maximum
Conversion Time
100
µ
s maximum (2 channels/scan)
Power Budget Requirement
80 mA @9V
External Power Supply
24 VDC,
?
10%, 170 mA, class 2
Operating Temperature
32
°
to 140
°
F (0
°
to 60
_
C)
Storage Temperature
--4
°
to 158
°
F (--20
°
to 70
_
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
The D3--02DA Analog Output appears as a 16-point module. The module can be
installed in any slot configured for 16 points. See the DL305 User Manual for details
on using 16 point modules in DL305 systems. The limitation on the number of analog
modules are:
S
For local and expansion systems, the available power budget and
16-point module usage are the limiting factors.
Analog Output
Configuration
Requirements