2--2
D3--04AD 4-Channel Analog Input
Module Specifications
The following table provides the specifications for the D3--04AD Analog Input
Module. Review these specifications to make sure the module meets your
application requirements.
Number of Channels
4
Input Ranges
1 -- 5V, 4 -- 20 mA
Resolution
8 bit (1 in 256)
Channel Isolation
Non-isolated (one common)
Input Type
Differential or Single ended
Input Impedance
1 M
O
minimum, voltage
250
O
current
Absolute Maximum Ratings
0 -- +10V maximum, voltage
0 -- 30 mA maximum, current
Linearity
?
0.8% maximum
Accuracy vs. Temperature
?
70 ppm /
_
C maximum
Maximim Inaccuracy
1% maximum at 25
_
C
Conversion Method
Sequential comparison
Conversion Time
2 ms maximum
Power Budget Requirement
55 mA @ 9V
External Power Supply
24 VDC,
?
10%, 65 mA, class 2
Operating Temperature
32
°
to 140
°
F (0
°
to 60
_
C)
Storage Temperature
--4
°
to 158
°
F (--20
°
to 70
_
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
Noise Rejection Ratio
Normal mode: --6 dB/250Hz
Common mode: 60dB/60Hz (--5 to 10V)
The D3--04AD Analog Input appears as a 16-point module. The module can be
installed in any slot configured for 16 points. See the DL305 User Manual for details
on using 16 point modules in DL305 systems. The limitation on the number of analog
modules are:
S
For local and expansion systems, the available power budget and
16-point module usage are the limiting factors.
Analog Input
Configuration
Requirements