F3--04ADS 4-Channel Isolated Analog Input
As you examin the jumper settings, notice there are jumpers for each individual
channel. These jumpers allow you to select the type of signal (voltage or current) and
the range of the signal. The following tables show the jumper selections for the
various ranges. Only channel 1 is used in the example, but all channels must be set.
NOTE:
The Polarity jumper selects Unipolar or Bipolar operation for all channels.
Bipolar Signal Range
Jumper Settings
--5 VDC to +5 VDC
(--20 to +20 mA)
--10 VDC to +10 VDC
Unipolar Signal Range
Jumper Settings
4 to 20 mA
(1 VDC to 5 VDC, remove the cur-
rent jumper)
0 VDC to +5 VDC
(0 to +20 mA, install the current
jumper)
0 VDC to +10 VDC
Selecting Input
Signal Ranges
1
Polarity
Uni Bi
Channel 1 Ranges
Current Jumper
1
Polarity
Uni Bi
Channel 1 Ranges
Current Jumper
1
Polarity
Uni Bi
Channel 1 Ranges
Current Jumper
1
Polarity
Uni Bi
Channel 1 Ranges
Current Jumper
1
Polarity
Uni Bi
Channel 1 Ranges
Current Jumper