F3--04ADS 4-Channel Isolated Analog Input
Module Specifications
The following table provides the specifications for the F3--04ADS Analog Input
Module. Make sure the module meets your application requirements.
Number of Channels
4, isolated
Input Ranges
0 -- 5V, 0 -- 10V, 1 -- 5V,
?
5V,
?
10V,
0 -- 20 mA, 4 -- 20 mA
Resolution
12 bit (1 in 4096)
Input Type
Differential
Max. Common mode voltage
?
750V peak continuous transformer isolation
Noise Rejection Ratio
Common mode: --100 dB at 60Hz
Active Low-pass Filtering
--3 dB at 10Hz, --12 dB per octave
Input Impedance
250
O
?
0.1%, 1/2W current input
200K
O
voltage input
Absolute Maximum Ratings
?
40 mA, current input
?
100V, voltage input
Conversion Time
1 channel per scan, successive
approximation, AD574
Linearity Error
?
1 count (0.03% of full scale) maximum
Full Scale Calibration Error
?
9 counts maximum
Offset Calibration Error
?
4 counts maximum, bipolar ranges
?
2 counts maximum, unipolar ranges
Accuracy vs. Temperature
57 ppm /
_
C maximum full scale
Recommended Fuse
0.032 A, Series 217 fast-acting, current inputs
Power Budget Requirement
183 mA @ 9 VDC, 50 mA @ 24 VDC
External Power Supply
None required
Operating Temperature
32
°
to 140
°
F (0
°
to 60
_
C)
Storage Temperature
--4
°
to 158
°
F (--20
°
to 70
_
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
The F3--04ADS Analog Input appears as a 16-point module. The module can be
installed in any slot configured for 16 points. See the DL305 User Manual for details
on using 16 point modules in DL305 systems. The limitation on the number of analog
modules are:
S
The module should not be placed in the last slot of a rack (due to size
constraints.)
S
For local and expansion systems, the available power budget and
16-point module usage are the limiting factors.
Analog Input
Configuration
Requirements