F
3-
-0
4D
A
S
4
C
h.
Is
ol
at
ed
A
na
lo
g
O
ut
.
8--10
F3--04DAS 4-Channel Isolated Analog Output
Module Operation
Before you begin writing the control program, it is important to take a few minutes to
understand how the module processes and represents the analog signals.
The F3--04DAS module can update one channel per CPU scan. Your RLL program
selects the channel to update, so you have complete flexibility in solving your
application requirements.
Channel 1
Scan N
Calculate the data
Write data
I/O Update
Execute Application Program
Channel 3
Scan N+1
Channel 1
Scan N+2
Channel 4
Scan N+3
Scan N+4
Scan
Channel 2
Channel Scanning