Automatic Systems
Logic D1 v06-02-en0802.doc
ERB-PM
Technical manual
10/31
2.3.
Operation mode parameters.
The DIP-switches of SW4 (
1:15
) permit the following choices of functions:
DIP 1
DIP 2
Choice of the operation mode of the barrier
(see chart below)
DIP 3 ON
Mechanical test (open and close)
DIP 4 ON
Activation of parameter 13: "Power failure mode"
DIP 5 ON
Send operation parameters to output RS232.
This option is used to diagnose breakdowns.
DIP 6 ON
Simulation of the jump on the three STOP commands if
none is wired.
DIP 7 OFF
Not allocated:
always OFF
DIP 8 ON
Access to the programming of the logic board
Combination chart of DIP1 and DIP2
DIP 1
DIP 2
Mode
Comments
OFF
OFF
0
“Normal”: opening and closing are wired.
The input OVB (X8, terminal 3, 23 or 25) controls the opening while
the input FRB (X8, terminal 5, 27 or 29) controls the closing.
OFF
ON
1
“Maintained”: only input OVB will wired.
A closed contact on the input OVB (X8, terminal 3, 23 or 25) controls the
opening and this contact, when opened, start the closing.
No connection can be realised on the input FRB.
The opening command must be maintained to open the barrier; as soon as
this command is released, the barrier closes.
ON
OFF
2
"Step-by-step": only input OVB will wired.
One pulse on the input OVB (X8, terminal 3, 23 or 25) reverses the
command in progress. No connection can be realised on the input FRB.