87
NOTES
•
To move within a screen, use the arrow keys. Screens that show a scroll indicator are
longer than 4 rows.
•
To jump to another screen, press a softkey. A
[Prev]
link jumps to the previous
screen.
•
The BAC
view
6
's screen goes dim after 10 minutes of inactivity. Press any key except
MUTE
or
FN
, to activate the screen.
•
To adjust the contrast of the display, turn the contrast screw on top of the BAC
view
6
clockwise to lighten the display or counterclockwise to darken it.
This BACview
6
screen...
Lets you...
Home
View:
•
Zone temperature
•
Heating and cooling output
Setpts
Adjust the heating and cooling setpoints
PID
Adjust the PID gains
Misc
•
Adjust heating and cooling limits
•
Adjust minimum outside air damper position
•
Change reversing valve action
Clockset
Adjust the Room Controller's real time clock
To change a property
1
Use the arrow keys to highlight the property value you want to edit.
2
Press
ENTER
.
3
Press the left or right arrow key to move the cursor under the character you want to
change.
4
Do one of the following:
○
Press a number key.
○
Press the
DECR
or
INCR
softkey to cycle through binary or multi-state options or
to decrease or increase a number.
○
Press the
CANCEL
softkey to restore the original value.