30
•
Acceptable voltage drop in the wire from the controller to the controlled device
•
Resistance (Ohms) of the chosen wire gauge
•
Maximum current (Amps) the controlled device requires to operate
1
Verify that the Room Controller's power and communications connections work
properly.
2
Remove power from the Room Controller.
3
Connect input and output wiring to the Room Controller’s screw terminals. See the
control program's point list in Appendix B (page 42) to determine which input and
output numbers to use.
Analog Output 1
Analog Output 2
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
Digital Output 5
Digital Output 6
Input 1
Input 2
Input 3
Input 4
Ground
Ground
UI-3 Jumper
UI-4 Jumper
9
87
6
5 4
32
1
0
9
87
6
5 4
32
1
0
1 2 3 4 5 6 7 8
O
N
4
Set the
UI-3
and
UI-4
jumpers.
If...
Is used for...
Then...
Input 3
Dry contact
Put on
UI-3 Jumper
0-5 Vdc
Remove
UI-3 Jumper
Input 4
Dry contact
Put on
UI-4 Jumper
0-5 Vdc
Remove
UI-4 Jumper
5
Apply power to the Room Controller.
To wire inputs
and outputs