![Automated Logic RC642 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520035.webp)
31
For a stand-alone Room Controller, you can use one of the 12 built-in control programs or
download a custom control program.
See Appendix B (page 42) for a full description of each control program.
1
Remove power from the Room Controller.
2
Set DIP switch 8 to
On
to have the Room Controller operate as a stand-alone unit.
3
Set the rotary switches to the desired control program. See table below.
WARNING
Do not set the switches to 0,0.
4
Put the
Format
jumper on.
Format
jumper
98
7 6
5
4 3
21
0
98
7 6
5
4 3
21
0
1 2 3 4 5 6 7 8
O
N
10’s
1’s
5
Apply power to the Room Controller.
6
Verify that the Room Controller displays the zone temperature.
7
Remove the
Format
jumper.
To use this
control program...
With these features...
Set the rotary
switches to...
100% outside air
unit
•
Scheduled operation
•
Freeze protection (optional) – Requires
sensor
•
Smoke detection (optional) – Requires
sensor
•
Single speed fan
•
Modulating chilled water valve (analog) OR
•
Modulating hot water valve (analog)
2-stage cooling
OR
•
2-position outdoor air damper
2-stage heating
•
Fan status monitor (optional) – Requires
sensor
•
Discharge temperature limit control
(optional) – Requires sensor
01
Selecting or downloading a control program
To select a built-
in control
program