4
If the Room Controller is installed in a WebCTRL system, you can wire RS sensors to it.
To this model's
Rnet port...
You can wire these combinations of RS room sensors...
RC642
•
1 RS Plus, RS Pro, or RS Pro-F
•
1–3 RS Standards
•
1–3 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
RC642D
1-4 RS Standards
NOTE
The RC642's internal sensor counts as an RS Standard on the Rnet. The RC642D's
internal sensor counts as an RS Pro on the Rnet.
To start up and troubleshoot the Room Controller, you can temporarily connect the
following items to its Local Access port:
•
The BACview
6
Handheld. See its
Technical Instructions
A laptop running Virtual BACview, an application that simulates the BACview
6
. Virtual
BACview is included with WebCTRL v4 or later.
To use the above with...
Built-in control programs
See Appendix C -
Editing properties in built-in control
programs
Custom control programs You must:
1. Create a BACview screen file in ViewBuilder.
2. Enter the screen file name in the Room Controller's
Properties
box in SiteBuilder.
3. Download the control program to the Room Controller.
NOTES
•
Disconnect the BAC
view
immediately after editing the properties. The BAC
view
connection heats up the Room Controller, affecting its temperature reading. The
recovery time depends on how long the BAC
view
was connected.
•
Room Controller does not support a BACview wired to its
Rnet
port.
Room sensors
BACviews