![Automated Logic RC642 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520042.webp)
38
2
To set the beginning time for the schedule, tap
or
to change the minutes
or hold down the buttons to change the hour.
3
Press
SCHEDULE
again and set the beginning time for the
Unoccupied
schedule.
NOTE
To delete a schedule, set
Occupied
and
Unoccupied
to the same time.
If you have problems mounting, wiring, or addressing the Room Controller, contact ALC
Technical Support.
The LED's on the Room Controller show the status of certain functions.
Error LED
Run LED
Power LED
98
7 6
5
4 3
21
0
98
7 6
5
4 3
21
0
1 2 3 4 5 6 7 8
O
N
If the
Power
LED is on, the Room Controller has power.
The
Run
and
Error
LED's indicate controller and network status.
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes,
alternating with
Run
LED
Five minute auto-restart delay
after system error
2 flashes per second
3 flashes,
then off
The controller has just been
formatted
2 flashes per second
4 flashes,
then pause
Two or more devices on this
network have the same
ARC156 network address
2 flashes per second
1 flash per second
The controller is alone on the
network
Troubleshooting a stand-alone Room Controller
LED's