33
To use this
control program...
With these features...
Set the rotary
switches to...
Air source heat
pump – intermittent
fan - reverse to cool
•
Scheduled operation
•
Single-speed fan – Cycles on and off with
heating or cooling
•
2-stage compressor
•
2-stage supplemental heat (optional)
•
Discharge temperature limit control (optional)
– Requires sensor
NOTE
This control program is identical to #04
above except that cooling is provided when the
reversing valve output closes.
05
Convective/fin tube
heater
•
Scheduled operation
•
HW valve modulation –
0–10v OR
06
120 sec floating motor
Fan coil unit –
2-speed fan,
modulated or
2-stage cooling
and heating
•
Scheduled operation
•
Freeze protection (optional) – Requires
sensor
•
Smoke detection (optional) – Requires
sensor
•
Single or 2-speed fan
•
Modulating chilled water valve (analog) OR
•
Modulating hot water valve (analog)
2-stage cooling
OR
•
Fan status monitor (optional) – Requires
sensor
2-stage heating
•
Discharge temperature limit control (optional)
– Requires sensor
07
Fan coil unit –
3-speed fan,
2-stage or
modulated cooling,
1-stage or
modulated heating
•
Scheduled operation
•
Freeze protection (optional) – Requires
sensor
•
Smoke detection (optional) – Requires
sensor
•
3-speed speed fan
•
Modulating chilled water valve (analog) OR
•
Modulating hot water valve (analog)
2-stage cooling
OR
•
Fan status monitor (optional) – Requires
sensor
1-stage heating
•
Discharge temperature limit control (optional)
– Requires sensor
08