86
To edit
certain properties
(page 88) in a built-in control program, you can temporarily
connect the following items to the Room Controller's Local Access port:
•
The BAC
view
6
Handheld. See
To use a BACview6 Handheld
below.
•
A laptop running Virtual BAC
view
, an application that simulates the BAC
view
6
. Virtual
BAC
view
is included with WebCTRL v4 or later. To use Virtual BAC
view
, see
Help
in the
application.
When you select a built-in control program using the rotary switches, the appropriate built-
in BAC
view
screens are also selected.
NOTES
•
Edited values are stored in the Room Controller's memory. The properties will return
to their default settings if you do either of the following:
○
Format the Room Controller
○
Remove power and the battery from the Room Controller.
•
Disconnect the BAC
view
immediately after editing the properties. The BAC
view
connection heats up the Room Controller, affecting its temperature reading. The
recovery time depends on how long the BAC
view
was connected.
Appendix C - Editing properties in a built-in control program
To use a BACview6
Handheld