![AUTOFLAME Mini Mk8 M.M. Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/autoflame/mini-mk8-m-m/mini-mk8-m-m_installation-and-commissioning-manual_3021294046.webp)
46
85
0
Modulation Exerciser Period:
Repeatedly run between high and low flame. The
higer the value, the longer high/low flame position is held for.
控制作业时限:在高火焰和低火焰之间重复运行。本参数值越大,保持在高火
焰和低火焰位置运行的时段越长。
0 - 3600
Seconds
秒
86
85
IBS Change Down Threshold:
If the combined firing rate of the last 2 boilers is
below this value, then the last last lag boiler will go into into the next stage
(standby, warming, or off) depending on how the sequencing is set.
智能锅炉排序降速阈值:当排序最接近的两台在线滞后锅炉的联合燃烧率低于
这个数值时,根据排序情况两台滞后锅炉的后一台将进入下一阶段(待机,加
温,或者关闭)。
0 - 99
%
87
95
IBS Change Up Threshold:
If the firing rate of the first last boiler online is above
this value, then the next boile will come online and fire to meet the required
setpoint.
智能锅炉排序加速阈值:当排序最接近的在线滞后锅炉的燃烧率高于这个数
值,为了满足燃烧率要求下一台滞后锅炉将要上线运行。
0 - 100
%
88
1000
Outside Temperature Sensor Adjustment:
If the actual reading is too high set a
negative value to adjust, if the reading is too low set a positive value.
室外温度感应器调节:如果实际读数太高,应设置一个负数来调节;如果实际
读数太低,应设置一个正数来调节。
500 -
2000
Value 1000 = 100.0%
数值
1000 = 100.0%
89
0
Stat Exerciser Period:
控制点作业时限
0 - 3600
Seconds
秒
90
0
Unused.
未使用
91
0
Unused.
未使用
92
0
Unused.
未使用
93
0
Unused.
未使用
94
0
NO Upper Limit Offset:
This is an offset limit from the commissioned values, if the
NO is above this limit an alarm will occur.
NO
上限补偿值:这是调试数据的补偿极限值,当
NO
高于这个极限值时警报响
起。
0
Disabled.
参数关闭
1 - 200
ppm
95
0
Unused.
未使用
96
0
Exhaust Temperature Upper Limit Offset:
This is an offset limit from the
commissioned values
.
烟气温度上限补偿值:这是调试数据的补偿极限值。
0
Disabled.
参数关闭
1 - 999
deg C/ deg F
97
0
Exhaust Temperature Absolute Limit:
System checks for exhaust temperatures
higher than this value.
烟气温度绝对上限:系统检查烟气温度是否高于该上限值。
0
Disabled.
参数关闭
1 - 999
deg C/ deg F
98
0
Unused.
未使用
99
0
Graceful Shutdown:
In changing/ deselecting fuels, the burner will modulate to low
fire and shut down, recycle the system and then changes fuels.
燃料转换时的关机:在转换
/
取消燃料时,燃烧器会调节到低火和关机,随后进
入系统再循环和更换燃料。
0
Disabled.
Содержание Mini Mk8 M.M.
Страница 1: ...1...
Страница 6: ...6 1 1 Mini Mk8 M M MK8 1 1 1 Fixing Holes and Dimensions...
Страница 7: ...7 1 2 Wiring Schematic...
Страница 8: ...8...
Страница 15: ...15 1 4 Connection Between Mini Mk8 M M and Mk8 E G A Mk8 Mk8 E G A...
Страница 16: ...16 1 5 Connection Between Mini Mk8 M M and Mk7 D T I Mk8 Mk7 D T I...
Страница 17: ...17 1 6 Sequencing Connection Diagram Mk8...
Страница 53: ...53 3 3 3 Servomotors Direction Change...
Страница 85: ...85 Figure 3 7 iv Single Point Change Trim EGA The M M will store the trim values for this position EGA...
Страница 122: ...122 Notes...
Страница 123: ...123...
Страница 124: ...124...