27
31
100
Maximum Remote Setpoint (D.T.I./ Modbus):
最高远程设定值
(D.T.I./ Modbus):
5 - 9990
If Centigrade, Fahrenheit or PSI units effective.
使用单位是摄氏,华氏或者磅
/
平方英寸
0.5-
999.0
If Bar units effective.
使用单位是巴
32
20
Trim Delay:
After ignition, the E.G.A. does not sample for the period of time set in
this option (only relevant if E.G.A. is operational on system). This allows for the
combustion to stabilise before sampling commences. The timing starts at the
ignition point.
EGA
调节延时:点火后
E.G.A.
在本选项时长内不执行取样(仅在
E.G.A.
运行时有
效)。这是为了获得稳定的燃烧状态样本。计时始于点燃点。
0 - 250
Period (seconds) after ignition where no sampling takes place.
延时取样的时间段。
33
1
M.M. Identification:
Each M.M. within a sequence loop must have an individual ID.
Communication problems will occur within an IBS loop if incorrect or same IDs are
set for the M.M.s
控制模块标识:锅炉排序的每台锅炉控制模块都有一个标识号。控制模块标识
错误会导致锅炉排序的通讯问题。
1 -10
Identification number
锅炉标识号
34
0
Unused.
未使用
35
10
Sequence Scan Time:
This is the time period between sequencing requests from
the lead M.M. On the sequence scan time, the lead M.M. will demand lag burners
to be brought online or offline, depending on load requirements. See Parameters
86 and 87 for change down and up thresholds.
排序扫描时间:这是领头控制模块先后发出两次排序指令的间隔。在排序扫描
时间内领头控制模块会根据荷载情况来命令滞后锅炉的上线运行或者下线待
机。参见参数
86
和
87
来降低和升高阈值。
1 - 100
Sequence scan time (minutes).
排序扫描时间(分钟)
Note:
Accurate fuel flow metering must be entered for sequencing to operate. An
data cable (Beldon 501) must be connected between each M.M. unit (see sections
1.5 and 1.6 for correct connection).
注意:排序操作需要安装准确的燃料流量表。各控制模块必须用数据线
(Beldon
501)
连接(关于正确连接请参见章节
1.5
和
1.6
)
36
0
Sensor Selection (Mk7 E.G.A. only):
Available when using an E.G.A. System fitted
with NO2 and SO2 cells. The following option selects the type of additional cells
used.
感应器选择(只用于
Mk7 E.G.A.
)
:
该选项只在
E.G.A.
系统配有
NO2 and SO2
传感
器时有效。该选项选择额外使用的感应器类型。
0
No optional sensor.
无额外感应器
1
NO2 only.
仅
NO2
感应器
2
SO2 only.
仅
SO2
感应器
3
NO2 and SO2.
NO2 and SO2
37
0
Derivative Time:
The time taken to add/ remove additional 10% to the firing rate
based on the actual value and the required value.
微分时间:
根据实际值和需求值的相对关系来添加或者减少
10%
燃烧率所需要
的时间。
0
Disabled
关闭选项
1- 200
Seconds.
秒
38
2
Derivative Deadband:
This the deadband is the margin above and below the
required setpoint in which no derivative control occurs.
微分静带:微分静带是处于设定点上方和下方的规定区域。在这个区域不发生
燃烧率的添加和减少。
0 - 15
If Centigrade, Fahrenheit or PSI units effective.
使用单位是摄氏,华氏或者磅
/
平方英寸
0 - 1.5
If Bar units effective.
Содержание Mini Mk8 M.M.
Страница 1: ...1...
Страница 6: ...6 1 1 Mini Mk8 M M MK8 1 1 1 Fixing Holes and Dimensions...
Страница 7: ...7 1 2 Wiring Schematic...
Страница 8: ...8...
Страница 15: ...15 1 4 Connection Between Mini Mk8 M M and Mk8 E G A Mk8 Mk8 E G A...
Страница 16: ...16 1 5 Connection Between Mini Mk8 M M and Mk7 D T I Mk8 Mk7 D T I...
Страница 17: ...17 1 6 Sequencing Connection Diagram Mk8...
Страница 53: ...53 3 3 3 Servomotors Direction Change...
Страница 85: ...85 Figure 3 7 iv Single Point Change Trim EGA The M M will store the trim values for this position EGA...
Страница 122: ...122 Notes...
Страница 123: ...123...
Страница 124: ...124...